Standard Products


Design Verified Main Distribution Panel/ LVP5000

LVP 5000

Our standing type LVP series panels have proven their reliability through the desing verification tests according to the standart IEC 61439-1 / 2 (2011) ( TS EN 61439-1 / 2 (2013)). LVP series also offers our customers many partitioning options up to the last point FORM4b- type7 with its new design with special busbar and isolator structure which has 100kA/1s shorth circuit withstand current and 5000A current capacity.

STANDART TS EN 61439-1/2 (2013)
TYPE LVP5000
LOCATION TYPE INDOOR
RATED CURRENT In (A) 5000A
RATED OPERATIONAL VOLTAGE Ue (V) 400V AC
RATED FREQUENCY fn (Hz) 50 Hz
RATED INSULATION VOLTAGE Ui 690 V
RATED IMPULS WITHSTAND VOLTAGE Uimp 8 kV
RATED AUXILARY VOLTAGE Uaux 220V AC
RATED SHORTHTIME WITHSTAND CURRENT Icw 100 kA/ 1 sec. (main busbar)
RATED DEGREE OF PROTECTION IP 32 - IP 44
RATED DEGREE OF PROTECTION (Internal parts) IP 2X
MIN. AMBIENT TEMPERATURE (°C) INDOOR –5 °C
  OUTDOOR –25 °C
MAX. AMBIENT TEMPERATURE (°C) +40 °C
MAX. RELATIVE HUMUNITY INDOOR %50 +40 °C
  OUTDOOR %100 +25 °C
POLLUTION DEGREE 3-(Material group IIIa)
RATED MECHANICAL IMPACT CODE IK 10
EMC PERFORMANCE CATEGORY ENVIROMENT A
COOLING NATURAL
EARTING SYSTEM TN-S
THE FORM OF INTERNAL SEPERATION FORM 4b / TYPE 7